E0 |
Protection devices activated. |
E1 |
Defective Printed Circuit Board (PCB) – outdoor unit. |
E3 |
Actuation of High Pressure Switch (HPS). |
E4 |
Actuation of Low Pressure Switch (LPS). |
E5 |
Inverter compressor motor overheating. |
E6 |
STD compressor motor overcurrent/lock. |
E7 |
Malfunctioning outdoor unit fan motor system. |
E8 |
Overcurrent of inverter compressor. |
E9 |
Malfunctioning electronic expansion valve coil. |
EA |
Malfunctioning four way valve or cool/heat switch. |
EC |
Malfunction in the entering water temperature. |
F3 |
Malfunction in discharge pipe temperature. |
F6 |
Abnormal high pressure or refrigerant overcharged. |
H0 |
Malfunctioning sensor system of compressor. |
H1 |
Malfunctioning room temperature sensor or humidifier unit damper. |
H3 |
Malfunctioning high pressure switch (HPS). |
H4 |
Malfunctioning low pressure switch (LPS). |
H5 |
Malfunctioning compressor motor overload thermistor. |
H6 |
Malfunctioning position detection sensor. |
H7 |
Malfunctioning outdoor unit fan motor signal. |
H8 |
Malfunctioning compressor input (CT) system. |
H9 |
Malfunctioning outdoor air thermistor. |
HC |
Malfunctioning hot water temperature thermistor. |
HF |
Alarm in thermal storage unit or storage controller. |
HJ |
Malfunctioning thermal storage tank water level. |
J1 |
Malfunctioning pressure sensor. |
J2 |
Malfunctioning current sensor of compressor. |
J3 |
Malfunction in the discharge pipe thermistor. |
J4 |
Malfunction of the low pressure equivalent saturated temperature sensor system. |
J5 |
Malfunction in the suction pipe thermistor |
J6 |
Malfunction in the heat exchanger thermistor. |
J7/J8/J9 |
Malfunction in the thermistor – refrigerant circuit. |
JA/JC |
Malfunctioning high pressure sensor. |
JE |
Malfunctioning oil pressure sensor or sub-tank thermistor. |
JF |
Malfunctioning oil level sensor or heating heat exchanger thermistor. |
L0 |
Malfunction of the inverter system. |
L1 |
Malfunction of inverter PCB. |
L3 |
EL. COMPO. Box temperature rise. |
L4 |
Malfunction of inverter radiation temperature rise. |
L5 |
Inverter instantaneous overcurrent – DC output. |
L6 |
Inverter instantaneous overcurrent – AC output. |
L8 |
Malfunction of overcurrent inverter compressor. |
L9 |
Malfunction of inverter compressor startup error. |
LA |
Malfunction of power transistor. |
LC |
Malfunction of connection between control and inverter PCB. |
M1 |
Malfunction of central remote controller PCB. |
M8 |
Malfunction of connection between optional controllers for centralized control. |
MA |
Improper combination of optional controllers for centralized control. |
MC |
Address duplication; improper setting. |
P0 |
Shortage of refrigerant amount in the thermal storage unit. |
P1 |
Power voltage imbalance or inverter PCB. |
P2 |
Automatic refrigerant charge operation stop. |
P3 |
Malfunction of thermistor in switch box. |
P4 |
Malfunction of radiation temperature sensor. |
P8 |
Heat exchanger freezing protection during automatic refrigerant charging. |
P9 |
Malfunction of fan motor in the humidifier unit. |
P9 |
Automatic refrigerant charge operation completed. |
PA |
Refrigerant cylinder during automatic refrigerant charging. |
PA |
Broken wire of heater in the humidifier unit. |
PC |
Refrigerant cylinder during automatic refrigerant charging. |
PE |
Automatic refrigerant charge operation nearly completed. |
PH |
Refrigerant cylinder during automatic refrigerant charging. |
PJ |
Malfunction of capacity setting (Outdoor unit PCB). |
PJ |
Malfunction of transmission between inverter and fan driver. |